Plan Review Notes
Plan Review Notes For Permit 99080036
Permit Number 99080036
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00APPROVED 11/17/99 NCD
 1)AIR ADMITTANCE VALVES NOT PERMITTED IN
 RETURN AIR PLENUM AREA PER 1997 SMC 609.
 1.3
 2)ANY A/C UNITS SERVING AREA USED FOR
 EGRESS SHALL BE SHUT DOWN BY DUCT SMOKE
 DETECTOR 1997 SMC 406.2
 3) EVERY ATTIC IN WHICH MECHANICAL EQUIP
 MENT IS INSTALLED SHALL BE ACCESSIBLE BY
 AN OPENING AS LARGE AS THE LARGEST PIECE
 OF EQUIPMENT BUT IN NO CASE LESS THAN
 22X36 INCHES 1997 SMC 304.4.1
 4)PROVIDE BACKDRAFT DAMPER AT EACH
 EXHAUST AIR OPENING NOT EQUIPPED WITH
 CEILING MOUNTED EXHAUST FAN WITH DAMPER
 TO PREVENT CARRYOVER INTO ROOM IF ROOF
 MOUNTED EXHAUST FAN IS NOT RUNNING SMC
 501.4