Plan Review Notes For Permit 99071834 |
Permit Number |
99071834 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | SIZING OF GAS LINES TO APPLIANCES SHALL | | COMPLY W/S.G.C. TABLE 305.4A. | | | | SUBMIT CORRECT BTU LOAD FOR FRYERS AND | | CORRECT TOTAL BTU LOAD FOR SYSTEM.(PLANS | | SHOW FRYERS AS 45,000 AND 90,000 BTU'S. | | | | LOCATION OF S.O.V. AND UNION ON GAS LINE | | SHALL COMPLY W/NFPA 54 SEC.5.5.4. |
|