Plan Review Notes
Plan Review Notes For Permit 99071834
Permit Number 99071834
Review Stop P
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00SIZING OF GAS LINES TO APPLIANCES SHALL
 COMPLY W/S.G.C. TABLE 305.4A.
  
 SUBMIT CORRECT BTU LOAD FOR FRYERS AND
 CORRECT TOTAL BTU LOAD FOR SYSTEM.(PLANS
 SHOW FRYERS AS 45,000 AND 90,000 BTU'S.
  
 LOCATION OF S.O.V. AND UNION ON GAS LINE
 SHALL COMPLY W/NFPA 54 SEC.5.5.4.