2001-01-08 00:00:00 | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | (REFER TO DEFINITIONS IN CHAPT.2 OF | | STANDARD PLUMBING CODE,AND SEC.501.7. | | | | A PAN AND DRAIN ARE REQ'D.FOR THE WATER | | HEATER PER SPC SEC.507.8.1--5O7.8.4. | | | | SHT.A-6.NOTE 11."M"COPPER IS NOT | | PERMITTED FOR U/G USE PER SPC COUNTYWIDE | | AMENDMENTS TO SPC SEC.611.3. | | | | INDICATE TYPE OF GAS AND PIPING BEING | | UTILIZED.STD.GAS CODE SEC.302. | | | | SIZE ALL SECTIONS OF THE GAS RISER | | DIAGRAM.STD. GAS CODE SEC.302. | | | | COMPLY W/TABLES 305.4A, 305.4B OF STD. | | GAS CODE FOR PROPER SIZING OF GAS | | SYSTEM. | | | | THERE ARE 2 COPIES OF SHT.A-6 SHOWING | | DIFFERENT PLBG.DRAWINGS.CLARIFY.SPC | | 104.2.1. | | | | SUBMIT AMOUNT OF TOILET FACILITIES IN | | THE BUILDING.COMPLY W/TABLE 407 OF SPC. | | | | DISHWASHER SHALL BE INDIRECTLY WASTED | | PER SPC SEC.804.2. | | | | FLOOR DRAINS & HANDSINKS SHALL DISCHARGE | | TO GREASY WASTE SYSTEM PER SPC SEC. | | 1004.4. | | | | FLOOR DRAINS ARE NOT PROPERLY VENTED & | | SHALL NOT EXCEED DISTANCES FROM VENT | | PER SPC TABLE 908. | | | | SUBMIT MANUF.SHEETS FOR GAS EQUIP.PER | | STD.GAS CODE SEC.402.1. |
|