Plan Review Notes For Permit 99071517 |
Permit Number |
99071517 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ***************PROVISO***************** | | | | 1)NOTE:NEED TO SUBMIT AIC RATING OF | | EQUIPMENT FROM FAULT CURRENT CALCU- | | -LATIONS. | | 2)NOET:ART,210-52D BATH RECEPTS. ARE TO | | BE ON 20AMP BRANCH CIRCUTS. | | 3)NOTE:NFPA-72 SMOKE DETECTORS REQ`D | | INSIDE AND OUTSIDE BEDROOMS. | | | | PLEASE HAVE SUBMITTED AND APPROVED | | BEFORE ROUGH ELEC.INSPECTION. |
|