Plan Review Notes For Permit 99071182 |
Permit Number |
99071182 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ****************PROVISO***************** | | | | NOTE:NEED AIC RATING OF EQUIPMENT FROM | | FAULT CURRENT CALCULATIONS. | | ART:110-9/215-5 | | NOTE: EQUIPMENT GROUNDING CONDUCTOR | | REQ`D FROM FIRST MEANS OF DISC.250-92/ | | 250-95 | | NOTE: GROUNDING ELECTRODE CONDUCTOR TO | | COLD WATER PIPE ALSO. |
|