2001-01-08 00:00:00****************PROVISO*****************
  
 NOTE:NEED AIC RATING OF EQUIPMENT FROM
 FAULT CURRENT CALCULATIONS.
 ART:110-9/215-5
 NOTE: EQUIPMENT GROUNDING CONDUCTOR
 REQ`D FROM FIRST MEANS OF DISC.250-92/
 250-95
 NOTE: GROUNDING ELECTRODE CONDUCTOR TO
 COLD WATER PIPE ALSO.