Plan Review Notes
Plan Review Notes For Permit 99071111
Permit Number 99071111
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00MAX.OF 2 WATER CLOSETS PERMITTED ON 3"
 BUILDING DRAIN PER STD.PLBG.CODE TABLE
 714.1 FOOTNOTE #3.
  
 MIN.SIZE OF DRAINAGE PIPING UNDERGROUND
 SHALL BE 2" PER SPC SEC.714.4.
  
 FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC SEC.913.2
  
 KIT.SINK AND LAV.ARE NOT VENTED.COMPLY
 W/SPC SEC.901.2.