2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-THIS PERMIT DOESN'T INCLUDE THE
 OPTIONAL REAR PORCH.
 2-PROVIDE THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS AS PER SEC.1606 SBC
 3-PROVIDE PRODUCT APPROVALS FOR: BUTT
 GLAZING,FIREPLACE,WINDOW AND DOOR
 MULLIONS, BBQ, ENTRY DOOR ASSEMBLY,
 FIXED WINDOW AT FAMILY AND LIVING ROOM,
 ROOF TILE, SLIDING GLASS DOORS.
 4-PROVIDE SPECIFICATIONS OF HOW
 COMPLYING WITH SECTION 402.7 SGC 1997
 REGARDING INSTALLATION OF GAS APPLIANCE
 IN GARAGE.
 5-PROVIDE COMPLETE INSTALLATION DETAIL
 FOR HUNG AHU. SPECIFY ALL FASTENERS.
 6-PROVIDE COMPLETE SPECIFICATIONS AND
 DETAILS FOR MULLIONS AT FRONT WINDOWS.
 7-PROVIDE ATTIC ACCESS. SEC. 2309.6 SBC
 8-PROVIDE COMPLETE DETAIL/SECTION THRU
 CHIMNEY. SPECIFY ALL CONNECTORS AND
 CLEARANCES. SEC. 104.2.2 CITY AMENDMENT
 9-PROVIDE COMPLETE COLUMN SCHEDULE. SEE
 SHEET S1. SEC. 104.2.2 CITY AMENDMENTS.
 10-PROVIDE COMPLETE SPECIFICATIONS FOR
 CONSTRUCTION AT CEILINGS OF FRONT AND
 BACK PORCHES SEC. 2504.2 SBC 1997 AS
 PER ASTM C926 AND ASTM C1063.
 11-DESIGN LOADS ON SHEET S2 AND DESIGN
 CERTIFICATION FOR WIND LOAD COMPLIANCE
 FORM DON'T MATCH. REVISE AS REQUIRED.
 12-PROVIDE CEILING FANS AS PER CREDIT
 TAKEN IN THE ENERGY CALCULATIONS.
 13-FOOTING F2 IS ENCROACHING INTO THE
 NEIGHBOR'S PROPERTY AT ZERO LOT LINE.
 REVISE AS REQUIRED.
 14-STORM PANELS: REVISE INSTALLATION
 SCHEDULE. SEE OPENINGS #1,2,5,6,7
 15-SEE FLOOR PLANS FOR ADDITIONAL
 COMMENTS.
 16-PROVIDE COMPLETE SPECIFICATIONS AND
 DETAILS FOR BUTT GLAZING AS PER SECTION
 2405.3 AND 2406 SBC 1997.