Plan Review Notes For Permit 99071025 |
Permit Number |
99071025 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************** PROVISO ***************** | | 1) FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | REQUIRED PER 1994 SMC 406.1 AND 406.2 | | 2) NOTIFICATION OF FAN SHUT DOWN TO BE | | PER 1996 NFPA 4-4.4.2 OR 4-4.4.3 TIED TO | | BLDG FIRE ALARM SYSTEM OR IF NO BLDG | | SYSTEM, TIED TO HORN AND STROBE | | 3) BATH EXHAUST TO MEET 1994 SMC 503.3.2 |
|