Plan Review Notes For Permit 99070918 |
Permit Number |
99070918 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ########--PROVISO--##################### | | 1)DENTAL VACUUM AND AIR TO COMPLY WITH | | 1996 NFPA 99C | | 2)PIPING TO BE SLOPED MIN. 1/4" PER 10' | | TOWARD THE PUMP OR A SINGLE LOCATION | | BEFORE THE PUMP 4-5.2.2.5 CLEANOUT REQ'D | | 3)PIPING INTEGRITY TEST INCLUDING SOAP | | ALL JOINTS UNDER 150PSIG BEFORE CLOSING | | WALLS/FLOORS | | 4)24 HR PRESSURE TEST AT 15 PSIG REQ'D | | 5)AIR LINES TO BE BRAZED BY CERTIFIED | | BRAZER(NFPA 99C | | 6)COMPRESSED AIR PIPING TO BE INSTALLED | | PER 1996 NFPA 99C LEVEL 3 REQUIREMENTS | | 7)PIPE INTEGRITY TEST PER NOTE#3 ABOVE | | 8)24 HR PRESSURE TEST REQUIRED @ 150PSIG |
|