2001-01-08 00:00:00########--PROVISO--#####################
 1)DENTAL VACUUM AND AIR TO COMPLY WITH
 1996 NFPA 99C
 2)PIPING TO BE SLOPED MIN. 1/4" PER 10'
 TOWARD THE PUMP OR A SINGLE LOCATION
 BEFORE THE PUMP 4-5.2.2.5 CLEANOUT REQ'D
 3)PIPING INTEGRITY TEST INCLUDING SOAP
 ALL JOINTS UNDER 150PSIG BEFORE CLOSING
 WALLS/FLOORS
 4)24 HR PRESSURE TEST AT 15 PSIG REQ'D
 5)AIR LINES TO BE BRAZED BY CERTIFIED
 BRAZER(NFPA 99C
 6)COMPRESSED AIR PIPING TO BE INSTALLED
 PER 1996 NFPA 99C LEVEL 3 REQUIREMENTS
 7)PIPE INTEGRITY TEST PER NOTE#3 ABOVE
 8)24 HR PRESSURE TEST REQUIRED @ 150PSIG