2001-01-08 00:00:00 | CHECKLIST: |
| 1-PROVIDE ENERGY CALCULATIONS (USE FORM |
| 600A-97) AND MANUAL "J" CALCULATIONS. |
| 2-PROVIDE SOIL TEST REPORT AS PER SEC. |
| 1804.2.2 AND TABLE 1804.2.7.3 OF CITY |
| AMENDMENTS. |
| 3-DRAWNGS TO HAVE THE NAME AND ADDRESS |
| OF THE DESIGNER ENGINEER. SEC 104.2.1 |
| CITY AMENDMENTS. |
| 4-PAY THE IMPACT FEES TO THE COUNTY. |
| 5-PROVIDE SAFETY GLASS WHERE REQUIRED. |
| SEE PLANS FOR COMMENTS. SEC. 2405.2 |
| SBC 1997. |
| 6-PROVIDE THE DESIGN PRESSURES AT ALL |
| EXTERIOR OPENINGS. SEC. 1606 SBC 1997. |
| 7-STORM PANELS:*PROVIDE A COMPLETE |
| INSTALLATION SCHEDULE AND KEY PLAN. |
| *HIGHLIGHT SPECIFIC MOUNTING CONDITION |
| AND ANCHORS AND SPACING TO BE USED. |
| NOTE:THIS INFORMATION MAY BE FURNISHED |
| AT A LATER TIME, BUT, UNDER A SEPARATE |
| PERMIT. |
| 8-PROVIDE PRODUCT APPROVAL FOR ENTRY |
| DOOR AND REAR DOOR. |
| 9-FOOTING F1 TO BE 16" DEEP MIN. SEC. |
| 1804.1.3 SBC 1997 AND SEC. 1804.1.9 |
| CITY AMENDMENTS. |
| 10-REVISE NOTE #1 OF FOUNDATION NOTES. |
| PROVIDE MIN. 6 MIL VAPOR BARRIER. |
| SEC. 1909.2 SBC 1997. |
| 11-MEAN ROOF HEIGHT SPECIFIED IN THE |
| DESIGN CERTIFICATION FOR BUILDING CODE |
| COMPLIANCE FORM IS WRONG. REVISE AS |
| REQUIRED. |
| NOTE: IT IS RECOMMENDED TO WRITE THIS |
| INFORMATION ON THE PLANS, INSTEAD OF |
| FILLING A SEPARATE FORM. |
| |
| NOTE: |
| FLOOD ZONE AREA. WILL NEED TO PROVIDE |
| AN ELEVATION CERTIFICATE, AFTER |
| CONCRETE SLAB IS POURED. |