Plan Review Notes
Plan Review Notes For Permit 99061777
Permit Number 99061777
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CHECKLIST:
 1-PROVIDE ENERGY CALCULATIONS (USE FORM
 600A-97) AND MANUAL "J" CALCULATIONS.
 2-PROVIDE SOIL TEST REPORT AS PER SEC.
 1804.2.2 AND TABLE 1804.2.7.3 OF CITY
 AMENDMENTS.
 3-DRAWNGS TO HAVE THE NAME AND ADDRESS
 OF THE DESIGNER ENGINEER. SEC 104.2.1
 CITY AMENDMENTS.
 4-PAY THE IMPACT FEES TO THE COUNTY.
 5-PROVIDE SAFETY GLASS WHERE REQUIRED.
 SEE PLANS FOR COMMENTS. SEC. 2405.2
 SBC 1997.
 6-PROVIDE THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS. SEC. 1606 SBC 1997.
 7-STORM PANELS:*PROVIDE A COMPLETE
 INSTALLATION SCHEDULE AND KEY PLAN.
 *HIGHLIGHT SPECIFIC MOUNTING CONDITION
 AND ANCHORS AND SPACING TO BE USED.
 NOTE:THIS INFORMATION MAY BE FURNISHED
 AT A LATER TIME, BUT, UNDER A SEPARATE
 PERMIT.
 8-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR AND REAR DOOR.
 9-FOOTING F1 TO BE 16" DEEP MIN. SEC.
 1804.1.3 SBC 1997 AND SEC. 1804.1.9
 CITY AMENDMENTS.
 10-REVISE NOTE #1 OF FOUNDATION NOTES.
 PROVIDE MIN. 6 MIL VAPOR BARRIER.
 SEC. 1909.2 SBC 1997.
 11-MEAN ROOF HEIGHT SPECIFIED IN THE
 DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM IS WRONG. REVISE AS
 REQUIRED.
 NOTE: IT IS RECOMMENDED TO WRITE THIS
 INFORMATION ON THE PLANS, INSTEAD OF
 FILLING A SEPARATE FORM.
  
 NOTE:
 FLOOD ZONE AREA. WILL NEED TO PROVIDE
 AN ELEVATION CERTIFICATE, AFTER
 CONCRETE SLAB IS POURED.