2001-01-08 00:00:00****************PROVISO****************
  
 NOTE:NEED TO SUBMIT PLANS WITH AIC
 RATING FIGURED FROM FAULT CURRENT CAL-
 -CULATIONS.PLEASE DRAW ON PANEL SCHED.
 ART:110-9/215-5
 NOTE:RECEPTS. SERVING KITCHEN COUNTER
 ARE TO BE GFI/GFI PROTECTED.ART:210-8-A-
 6.
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.NFPA-72
 NOTE:EQUIPMENT GROUNDING CONDUCTOR REQ`D
 FROM MAIN DISC.TO PANEL.250-92/250-95
 NOTE:ART.210-52E RECEPTS.REQ`D FRONT
 AND BACK OF DWELLING.
 NOTE:GROUNDING ELECTRODE CONDUCTOR TO GO
 TO BLDG.STEEL AND CWP.
 NOTE:5 ROOMS SHOW BOXES IN THE CENTER OF
 THE ROOM. WHERE ARE THEY CONTROLLED? BY
 SWITCH?
  
 NEED TO HAVE THE ABOVE INFORMATION
 SUBMITTED AND APPROVED BEFORE ROUGH
 INSPECTION IS CALLED IN.