Plan Review Notes For Permit 99061777 |
Permit Number |
99061777 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ****************PROVISO**************** | | | | NOTE:NEED TO SUBMIT PLANS WITH AIC | | RATING FIGURED FROM FAULT CURRENT CAL- | | -CULATIONS.PLEASE DRAW ON PANEL SCHED. | | ART:110-9/215-5 | | NOTE:RECEPTS. SERVING KITCHEN COUNTER | | ARE TO BE GFI/GFI PROTECTED.ART:210-8-A- | | 6. | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | OUTSIDE BEDROOMS.NFPA-72 | | NOTE:EQUIPMENT GROUNDING CONDUCTOR REQ`D | | FROM MAIN DISC.TO PANEL.250-92/250-95 | | NOTE:ART.210-52E RECEPTS.REQ`D FRONT | | AND BACK OF DWELLING. | | NOTE:GROUNDING ELECTRODE CONDUCTOR TO GO | | TO BLDG.STEEL AND CWP. | | NOTE:5 ROOMS SHOW BOXES IN THE CENTER OF | | THE ROOM. WHERE ARE THEY CONTROLLED? BY | | SWITCH? | | | | NEED TO HAVE THE ABOVE INFORMATION | | SUBMITTED AND APPROVED BEFORE ROUGH | | INSPECTION IS CALLED IN. |
|