Plan Review Notes For Permit 99061775 |
Permit Number |
99061775 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *****************PROVISO**************** | | | | NOTE:NEED TO SUBMIT PLANS WITH AIC | | RATING FIGURED FROM FAULT CURRENT | | CALCULATIONS.PLEASE DRAW ON PANEL SCHED. | | ART:110-9/215-5 | | NOTE:RECEPTS.SERVING KITCHEN COUNTER | | SPACE ARE TO BE GFI/GFI PROTECTED.ART: | | 210-8-A-6 | | NOTE: SMOKE DETECTORS REQ`D INSIDE AND | | OUTSIDE BEDROOMS.NFPA-72 | | NOTE:EQUIPMENT GROUNDING CONDUCTOR REQ`D | | FROM MAIN DISC.TO PANEL. | | ART: 250-95/250-92 | | NOTE:RECEPTS.REQ`D FRONT AND BACK OF | | DWELLING UNITS ART:210-52E | | NOTE:GROUNDING ELECTRODE CONDUCTOR TO GO | | TOBLDG.STEEL AND CWP. | | NOTE:5 ROOMS SHOW CEILING BOXES IN THE | | CENTER OF THE ROOM.WHERE ARE THEY | | CONTROLLED FROM?? SWITCHED? | | | | NEED TO HAVE THE ABOVE INFORMATION | | SUBMITTED AND APPROVED BEFORE ROUGH | | INSPECTION IS CALLED IN. |
|