2001-01-08 00:00:00*****************PROVISO****************
  
 NOTE:NEED TO SUBMIT PLANS WITH AIC
 RATING FIGURED FROM FAULT CURRENT
 CALCULATIONS.PLEASE DRAW ON PANEL SCHED.
 ART:110-9/215-5
 NOTE:RECEPTS.SERVING KITCHEN COUNTER
 SPACE ARE TO BE GFI/GFI PROTECTED.ART:
 210-8-A-6
 NOTE: SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.NFPA-72
 NOTE:EQUIPMENT GROUNDING CONDUCTOR REQ`D
 FROM MAIN DISC.TO PANEL.
 ART: 250-95/250-92
 NOTE:RECEPTS.REQ`D FRONT AND BACK OF
 DWELLING UNITS ART:210-52E
 NOTE:GROUNDING ELECTRODE CONDUCTOR TO GO
 TOBLDG.STEEL AND CWP.
 NOTE:5 ROOMS SHOW CEILING BOXES IN THE
 CENTER OF THE ROOM.WHERE ARE THEY
 CONTROLLED FROM?? SWITCHED?
  
 NEED TO HAVE THE ABOVE INFORMATION
 SUBMITTED AND APPROVED BEFORE ROUGH
 INSPECTION IS CALLED IN.