2001-01-08 00:00:00***************PROVISO******************
  
 NOTE:NEED TO SUBMIT PLANS WITH AIC
 RATING FIGURED FROM FAULT CURRENT
 CALCULATIONS.PLEASE DRAW ON PANEL SCHED.
 ART:110-9/215-5
 NOTE:RECEPTS.SERVING KITCHEN COUNTER
 ARE TO GFI/GFI PROTCTED,ART:210-8-A-6.
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS AS PER NFPA-72
 NOTE:EQUIPMENT GROUNDING CONDUCTOR
 REQ`D FROM MAIN DISC.TO PANEL.250-92
 250-95.
 NOTE:ART:210-52E RECEPTS.REQ`D BACK AND
 FRONT OF DWELLING.
 NOTE:GROUNDING ELECTRODE CONDUCTOR
 REQ`D TO GO TO CWP BLDG.STEEL.
 NOTE:5 ROOMS SHOW CEILING BOXES.HOW ARE
 THEY CONTROLLED OR SWITCH?
  
 NEED TO HAVE THE ABOVE INFORMATION
 SUBMITTED AND APPROVED BEFORE ROUGH
 INSPECTION IS CALLED IN.