2001-01-08 00:00:00 | ***************PROVISO****************** | | | | NOTE:NEED TO SUBMIT PLANS WITH AIC | | RATING FIGURED FROM FAULT CURRENT | | CALCULATIONS.PLEASE DRAW ON PANEL SCHED. | | ART:110-9/215-5 | | NOTE:RECEPTS.SERVING KITCHEN COUNTER | | ARE TO GFI/GFI PROTCTED,ART:210-8-A-6. | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | OUTSIDE BEDROOMS AS PER NFPA-72 | | NOTE:EQUIPMENT GROUNDING CONDUCTOR | | REQ`D FROM MAIN DISC.TO PANEL.250-92 | | 250-95. | | NOTE:ART:210-52E RECEPTS.REQ`D BACK AND | | FRONT OF DWELLING. | | NOTE:GROUNDING ELECTRODE CONDUCTOR | | REQ`D TO GO TO CWP BLDG.STEEL. | | NOTE:5 ROOMS SHOW CEILING BOXES.HOW ARE | | THEY CONTROLLED OR SWITCH? | | | | NEED TO HAVE THE ABOVE INFORMATION | | SUBMITTED AND APPROVED BEFORE ROUGH | | INSPECTION IS CALLED IN. |
|