2001-01-08 00:00:00 | 1- PG. E-1SHOWS A REFERENCE TO THE |
| HEIGHT OF FIXTURES IN THE STAIRWELLS |
| AND CORIDOORS AT 74" LIFE SAFTEY 101 |
| HAS A MINIMUM OF 6'8" ABOVE FINISHED |
| FLOOR UNLESS IT IS FLUSH WITH THE WAL |
| |
| 2- PG. E-3 HAS A REFERENCE TO THE |
| LOCATION AND NUMBER OF SMOKE DETECTOR |
| IN THE UNITS NFPA 72 REQUIRES THEM TO |
| BE INSIDE AND OUTSIDE OF EACH BDRM. |
| THE NOTE REFERENCES THE FIRE DEPT. |
| THEY DONT DO ROUGH INSPECTIONS!! |
| DETECTORS WILL BE PER PLAN AND CODE. |
| 1996 NFPA 70 ADOPTED NFPA 72 WHICH |
| CALLS FOR THE DETECTORS AS STATED |
| ABOVE. |
| |
| PG. E-4 PANELS X, XR, AND HR SHOW NO |
| AIC RATINGS FOR THE PANEL AND BREAKER |
| PLEASE LIST IN THE DESCRIPTION OF THE |
| PANEL AS SHOWN ON OTHER PANELS |
| |
| PG E-4 GNEERATOR SHOWS THE MAIN ON THE |
| SECOND FLOOR!230-72(B) REQUIRES IT |
| TO BE WITH THE NORMAL MAINS BUT NOT |
| RIGHT NEXT TO THEM, REMOTE WHICH CAN |
| BE AS LITTLE AS 10'!!!! PER NFPA |
| |
| PG E-42500 AMP FEED TO SECOND FLOOR FOR |
| APT. MAINS NEEDS TO BE ENCASED IN |
| 2" OF CONCRETE, BRICK, OR TILE!!!!! |
| |
| PR E-4 SAME FOR THE FIRE PUMP!!!!!!!!! |
| |
| PG E-4 THERE IS ALSO NO REFERENCE TO THE |
| PLAQUES THAT ARE REQUIRED AT EACH OF |
| THE THREE SERVICES SHOWING THE |
| LOCATIONS OF THE OTHER SERVICES. |
| 230-2(E) |