Plan Review Notes
Plan Review Notes For Permit 99061677
Permit Number 99061677
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001- PG. E-1SHOWS A REFERENCE TO THE
 HEIGHT OF FIXTURES IN THE STAIRWELLS
 AND CORIDOORS AT 74" LIFE SAFTEY 101
 HAS A MINIMUM OF 6'8" ABOVE FINISHED
 FLOOR UNLESS IT IS FLUSH WITH THE WAL
  
 2- PG. E-3 HAS A REFERENCE TO THE
 LOCATION AND NUMBER OF SMOKE DETECTOR
 IN THE UNITS NFPA 72 REQUIRES THEM TO
 BE INSIDE AND OUTSIDE OF EACH BDRM.
 THE NOTE REFERENCES THE FIRE DEPT.
 THEY DONT DO ROUGH INSPECTIONS!!
 DETECTORS WILL BE PER PLAN AND CODE.
 1996 NFPA 70 ADOPTED NFPA 72 WHICH
 CALLS FOR THE DETECTORS AS STATED
 ABOVE.
  
 PG. E-4 PANELS X, XR, AND HR SHOW NO
 AIC RATINGS FOR THE PANEL AND BREAKER
 PLEASE LIST IN THE DESCRIPTION OF THE
 PANEL AS SHOWN ON OTHER PANELS
  
 PG E-4 GNEERATOR SHOWS THE MAIN ON THE
 SECOND FLOOR!230-72(B) REQUIRES IT
 TO BE WITH THE NORMAL MAINS BUT NOT
 RIGHT NEXT TO THEM, REMOTE WHICH CAN
 BE AS LITTLE AS 10'!!!! PER NFPA
  
 PG E-42500 AMP FEED TO SECOND FLOOR FOR
 APT. MAINS NEEDS TO BE ENCASED IN
 2" OF CONCRETE, BRICK, OR TILE!!!!!
  
 PR E-4 SAME FOR THE FIRE PUMP!!!!!!!!!
  
 PG E-4 THERE IS ALSO NO REFERENCE TO THE
 PLAQUES THAT ARE REQUIRED AT EACH OF
 THE THREE SERVICES SHOWING THE
 LOCATIONS OF THE OTHER SERVICES.
 230-2(E)