2001-01-08 00:00:00 | SHT.P-5.-UNITS"A","B" & "C" CORRECTLY |
| SIZE WATER LINES TO BATHROOM GROUPS. |
| OMPLY W/COUNTYWIDE AMENDMENTS TO SPC |
| SEC.607.7. |
| |
| SHT.P-6.-4" F.D. IN EMERG.GEN.ROOM |
| REQUIRES VENT.COMPLY W/SPC TABLE 908.1. |
| |
| SHT.P-6.-FLOOR DRAIN IN TRASH ROOM |
| REQUIRES VENT.COMPLY W/SPC TABLE 908.1. |
| |
| SHT.P-6.-STACKS #9,10,13,14,15,16,21,22, |
| 23,24,27,28.SIZE OF VERTICAL COMBINATION |
| WASTE AND VENT SYSTEM SHALL COMPLY W/SPC |
| SEC.911.4 AND TABLE 911.4 (BRANCH BEGINS |
| AS 6" AND REDUCES TO 5".NOTE:PIPE SIZE |
| TO REMAIN FULL SIZE THRU ROOF.) |
| |
| SHT.P-7.-WTR.HEATER DETAIL-PAN DRAIN BE |
| MIN.OF 1" PER SPC SEC.507.8.2. |
| |
| NOTE ON PLAN THAT SHOWER VALVES COMPLY |
| W/SPC TABLE 613. |
| |
| SHT.P-5.-SERVICE SINK ON GROUND FLR. |
| SHALL BE VALVED PER SPC SEC.610.4.1. |
| |
| SIZE OF GREASE TRAP AND OIL/SAND |
| INTERCEPTOR SHALL BE APPROVED BY CITY |
| OF WEST PALM BEACH UTILITIES DEPT. |
| CONTACT RODNEY COMPO AT(561)835-7423. |
| |
| RELIEF VENTS ARE REQ'D.IN THE DRAINAGE |
| SYSTEM PER SPC SEC.916. |
| |
| SHT.A-3.-DISTANCE OF WATER SERVICE FROM |
| BLDG.DRAIN OR SEWER SHALL COMPLY W/SPC |
| SEC.608.3, 608.4.(NOTE AREAS AT GREASE |
| TRAPS AND OIL /SAND INTERCEPTOR. |
| |
| SUBMIT PIPING ISOMETRIC FOR STORM |
| DRAINAGE SYSTEM. SPC 104.2.1. |
| |
| SUBMIT RISER DIAGRAM FOR SUMP PUMP |
| PIPING IN TRASH ROOM.COMPLY W/SPC SEC. |
| 717. |
| |
| SHOW DISTANCE OF INTERCEPTORS FROM |
| BLDG.COMPLY W/STANDARD BLDG.CODE SEC. |
| 1803.1.3.FOR EXCAVATIONS. |
| |
| A COMPLETE GAS DRAWING SHALL BE |
| SUBMITTED PRIOR TO ISSUANCE OF GAS |
| PERMIT PER STANDARD GAS CODE SEC.104.2.1 |