2001-01-08 00:00:00SHT.P-5.-UNITS"A","B" & "C" CORRECTLY
 SIZE WATER LINES TO BATHROOM GROUPS.
 OMPLY W/COUNTYWIDE AMENDMENTS TO SPC
 SEC.607.7.
  
 SHT.P-6.-4" F.D. IN EMERG.GEN.ROOM
 REQUIRES VENT.COMPLY W/SPC TABLE 908.1.
  
 SHT.P-6.-FLOOR DRAIN IN TRASH ROOM
 REQUIRES VENT.COMPLY W/SPC TABLE 908.1.
  
 SHT.P-6.-STACKS #9,10,13,14,15,16,21,22,
 23,24,27,28.SIZE OF VERTICAL COMBINATION
 WASTE AND VENT SYSTEM SHALL COMPLY W/SPC
 SEC.911.4 AND TABLE 911.4 (BRANCH BEGINS
 AS 6" AND REDUCES TO 5".NOTE:PIPE SIZE
 TO REMAIN FULL SIZE THRU ROOF.)
  
 SHT.P-7.-WTR.HEATER DETAIL-PAN DRAIN BE
 MIN.OF 1" PER SPC SEC.507.8.2.
  
 NOTE ON PLAN THAT SHOWER VALVES COMPLY
 W/SPC TABLE 613.
  
 SHT.P-5.-SERVICE SINK ON GROUND FLR.
 SHALL BE VALVED PER SPC SEC.610.4.1.
  
 SIZE OF GREASE TRAP AND OIL/SAND
 INTERCEPTOR SHALL BE APPROVED BY CITY
 OF WEST PALM BEACH UTILITIES DEPT.
 CONTACT RODNEY COMPO AT(561)835-7423.
  
 RELIEF VENTS ARE REQ'D.IN THE DRAINAGE
 SYSTEM PER SPC SEC.916.
  
 SHT.A-3.-DISTANCE OF WATER SERVICE FROM
 BLDG.DRAIN OR SEWER SHALL COMPLY W/SPC
 SEC.608.3, 608.4.(NOTE AREAS AT GREASE
 TRAPS AND OIL /SAND INTERCEPTOR.
  
 SUBMIT PIPING ISOMETRIC FOR STORM
 DRAINAGE SYSTEM. SPC 104.2.1.
  
 SUBMIT RISER DIAGRAM FOR SUMP PUMP
 PIPING IN TRASH ROOM.COMPLY W/SPC SEC.
 717.
  
 SHOW DISTANCE OF INTERCEPTORS FROM
 BLDG.COMPLY W/STANDARD BLDG.CODE SEC.
 1803.1.3.FOR EXCAVATIONS.
  
 A COMPLETE GAS DRAWING SHALL BE
 SUBMITTED PRIOR TO ISSUANCE OF GAS
 PERMIT PER STANDARD GAS CODE SEC.104.2.1