2001-01-08 00:00:00 | *************PROVISO******************* |
| |
| 1) DRYER VENT DUCTS TO RUN TO OUTSIDE OF |
| THE BUILDING. 1994 SMC 509.1 (1) DUCTS |
| SHALL NOT BE CONNECTED TO A VENT |
| CONNECTOR, GAS VENT, CHIMNEY, CRAWL |
| SPACE OR OTHER SIMILIAR CONCEALED SPACE. |
| THE EXCEPTION 1994 SMC 610.1.3(2) WHERE |
| BRANCH DUCTS CONNECT TO RETURN RISERS |
| IN WHICH THE AIR IS UPWARD AND SUBDUCTS |
| AT LEAST 22 INCHES LONG ARE CARRIED UP |
| INSIDE THE RISER AT EACH INLET.,DOES NOT |
| APPLY TO DRYER VENTS |
| 2) THE EXHAUST FAN FOR THE DRYER VENT |
| CHASE DOES NOT COMPLY WITH THE REQUIR- |
| MENTS OF 1994 SMC 509.3 THE WALL OR ROOF |
| CAP SHALL BE NONSCREENED WITH BACKDRAFT |
| DAMPER. |
| 3)OVERFLOW PROTECTION REQUIRED ON AHU'S |
| 4) EXHAUST FROM GENERATOR TO TERMINATE |
| MIN. 10 FT FROM PARKING AREAS, WINDOWS, |
| DOOR OR AIR INTAKE OPENINGS AND AT LEAST |
| 10 FT. ABOVE ADJOINING ABOVE ADJOINING |
| GRADE LEVEL, PER 1994 SMC 506.1 |
| 5) 1994 SMC 406.2 REQUIRES SYSTEMS SERV- |
| ING AREAS USED FOR EGRESS TO HAVE AUTO- |
| MATIC FAN SHUT DOWN. PROVIDE AUTOMATIC |
| FAN SHUT DOWN FOR AHU 4. |
| 6)1994 SMC 406.5 SPECIAL PROVISIONS FOR |
| HIGH RISE GROUP R BLDGS REQUIRES A SMOKE |
| DETECTOR INSTALLED IN THE DUCT AT EACH |
| CONNECTION TO A VERTICAL DUCT OR RISER |
| SERVING A RECIRCULATING AIR SYSTEM OF |
| MORE THAN ONE STORY. PROVIDE DETAIL OF |
| LOCATON AND TYPE DETECTOR.1994SBC412.2.1 |
| 7)PROVIDE INFORMATION ON SMOKE CONTROL |
| SHOWING COMPLIANCE WITH 1994 SBC 412.5 |