Plan Review Notes
Plan Review Notes For Permit 99061677
Permit Number 99061677
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************PROVISO*******************
  
 1) DRYER VENT DUCTS TO RUN TO OUTSIDE OF
 THE BUILDING. 1994 SMC 509.1 (1) DUCTS
 SHALL NOT BE CONNECTED TO A VENT
 CONNECTOR, GAS VENT, CHIMNEY, CRAWL
 SPACE OR OTHER SIMILIAR CONCEALED SPACE.
 THE EXCEPTION 1994 SMC 610.1.3(2) WHERE
 BRANCH DUCTS CONNECT TO RETURN RISERS
 IN WHICH THE AIR IS UPWARD AND SUBDUCTS
 AT LEAST 22 INCHES LONG ARE CARRIED UP
 INSIDE THE RISER AT EACH INLET.,DOES NOT
 APPLY TO DRYER VENTS
 2) THE EXHAUST FAN FOR THE DRYER VENT
 CHASE DOES NOT COMPLY WITH THE REQUIR-
 MENTS OF 1994 SMC 509.3 THE WALL OR ROOF
 CAP SHALL BE NONSCREENED WITH BACKDRAFT
 DAMPER.
 3)OVERFLOW PROTECTION REQUIRED ON AHU'S
 4) EXHAUST FROM GENERATOR TO TERMINATE
 MIN. 10 FT FROM PARKING AREAS, WINDOWS,
 DOOR OR AIR INTAKE OPENINGS AND AT LEAST
 10 FT. ABOVE ADJOINING ABOVE ADJOINING
 GRADE LEVEL, PER 1994 SMC 506.1
 5) 1994 SMC 406.2 REQUIRES SYSTEMS SERV-
 ING AREAS USED FOR EGRESS TO HAVE AUTO-
 MATIC FAN SHUT DOWN. PROVIDE AUTOMATIC
 FAN SHUT DOWN FOR AHU 4.
 6)1994 SMC 406.5 SPECIAL PROVISIONS FOR
 HIGH RISE GROUP R BLDGS REQUIRES A SMOKE
 DETECTOR INSTALLED IN THE DUCT AT EACH
 CONNECTION TO A VERTICAL DUCT OR RISER
 SERVING A RECIRCULATING AIR SYSTEM OF
 MORE THAN ONE STORY. PROVIDE DETAIL OF
 LOCATON AND TYPE DETECTOR.1994SBC412.2.1
 7)PROVIDE INFORMATION ON SMOKE CONTROL
 SHOWING COMPLIANCE WITH 1994 SBC 412.5