Plan Review Notes
Plan Review Notes For Permit 99061605
Permit Number 99061605
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00INDICATE TYPE OF PIPING TO GRILL & POOL
 HTR.COMPLY W/STD.GAS CODE SEC.306.1.
  
 INDICATE CORRECT SIZING TABLES FOR GAS
 PIPING SYSTEM PER STD.GAS CODE SEC.305.
  
 RE-CALCULATE DISTANCE & BTU LOAD FOR
 PROPER SIZING AND SHOW DELIVERY PRESSURE
 TO SYSTEM. STD.GAS CODE SEC.305.4.