2001-01-08 00:00:00 | *************DENIED******************* |
| |
| NOTE:NEED TO SUBMIT NEW LOAD |
| CACULATIONS AS PER ART:220-3-D-1 |
| NEED TO SUBMIT EXISTING RISER DIAGRAM |
| TO INCLUDE WIRE SIZE,CONDUIT SIZES, |
| PANEL SIZE AND GROUNDING SYSTEM. |
| NOTE:ART:210-70 WHICH REQ`S LIGHT AT |
| MEANS OF EGRESS FROM THE STUDY. |
| SAME OUTSIDE LIGHT MAY BE SWITCHED ON |
| 3-WAY FROM ADJOINING ROOM. |
| |
| ***************PROVISO****************** |
| |
| 1)NOTE:FIRST SET OF PLANS HAD CORRECTION |
| FOR MEANS OF EGRESS LIGHTING ART:210-70 |
| STILL SHOWS NO MEANS OF EGRESS LIGHTING |
| AND HOW THEY ARE BEING SWITCHED. |
| 2)NOTE;1996 NFPA 2-2.1.1.1 REQ`S |
| SMOKE DETECTORS INSIDE AND OUTSIDE |
| BEDROOMS FOR ANY NEW BUILDING. |
| 3)NOTE:ART;210-63 REQ`S RECEPTS.FOR A/C |
| EQUIPMENT.NOTE LOCATION DRAWN ON PLANS. |
| 4)NOTE:FIRST SET OF PLANS DID NOT SHOW |
| SERVICE CHANGE.THE SUBMITTED RISER |
| DIAGRAM IS NOT COMPLETE AS TO THE |
| FOLLOWING CODE ARTS;215-5 AND 110-9 |
| PLEASE SUBMIT TO SHOW RISER CONDUIT |
| SIZE,WIRE SIZESUFFICIENT FOR SERVICE. |
| NOTE:GROUNDING ELECTRODE CONDUCTOR TO |
| GROUND ROD,COLD WATER PIPE AND NEW |
| BLDG.STEEL AS PER ART:250-81 |
| NOTE:SUBMIT AIC RATING OF NEW SERVICE |
| FIGURED FROM FAULT CURRENT CALCULATIONS. |
| |
| PLEASE HAVE ALL THE ABOVE ITEMS DONE |
| AND SUBMITTED FOR APPROVAL BEFORE FIRST |
| ELECTRICAL INSPECTION. |