Plan Review Notes
Plan Review Notes For Permit 99061517
Permit Number 99061517
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************DENIED*******************
  
 NOTE:NEED TO SUBMIT NEW LOAD
 CACULATIONS AS PER ART:220-3-D-1
 NEED TO SUBMIT EXISTING RISER DIAGRAM
 TO INCLUDE WIRE SIZE,CONDUIT SIZES,
 PANEL SIZE AND GROUNDING SYSTEM.
 NOTE:ART:210-70 WHICH REQ`S LIGHT AT
 MEANS OF EGRESS FROM THE STUDY.
 SAME OUTSIDE LIGHT MAY BE SWITCHED ON
 3-WAY FROM ADJOINING ROOM.
  
 ***************PROVISO******************
  
 1)NOTE:FIRST SET OF PLANS HAD CORRECTION
 FOR MEANS OF EGRESS LIGHTING ART:210-70
 STILL SHOWS NO MEANS OF EGRESS LIGHTING
 AND HOW THEY ARE BEING SWITCHED.
 2)NOTE;1996 NFPA 2-2.1.1.1 REQ`S
 SMOKE DETECTORS INSIDE AND OUTSIDE
 BEDROOMS FOR ANY NEW BUILDING.
 3)NOTE:ART;210-63 REQ`S RECEPTS.FOR A/C
 EQUIPMENT.NOTE LOCATION DRAWN ON PLANS.
 4)NOTE:FIRST SET OF PLANS DID NOT SHOW
 SERVICE CHANGE.THE SUBMITTED RISER
 DIAGRAM IS NOT COMPLETE AS TO THE
 FOLLOWING CODE ARTS;215-5 AND 110-9
 PLEASE SUBMIT TO SHOW RISER CONDUIT
 SIZE,WIRE SIZESUFFICIENT FOR SERVICE.
 NOTE:GROUNDING ELECTRODE CONDUCTOR TO
 GROUND ROD,COLD WATER PIPE AND NEW
 BLDG.STEEL AS PER ART:250-81
 NOTE:SUBMIT AIC RATING OF NEW SERVICE
 FIGURED FROM FAULT CURRENT CALCULATIONS.
  
 PLEASE HAVE ALL THE ABOVE ITEMS DONE
 AND SUBMITTED FOR APPROVAL BEFORE FIRST
 ELECTRICAL INSPECTION.