Plan Review Notes For Permit 99061465 |
Permit Number |
99061465 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | SHOW CLEAR DIMENSIONS OF HANDICAP TOILET | | ROMMS ON PLANS.COMPLY W/F.A.C.B.C.SEC. | | 4.16.2. | | | | SHT.A-8-HEIGHT OF H.C.WATER CLOSETS | | SHALL COMPLY W/F.A.C.B.C.SEC.4.16.3. | | | | WAINSCOTING IN TOILET ROOMS SHALL COMPLY | | W/STD.BLDG.CODE SEC.1204.2. | | | | HEIGHT OF GRAB BARS SHALL COMPLY W/ | | F.A.C.B.C. SEC.4.16.4. | | | | NOT MORE THAN 2 FIXTURES SHALL BE | | CONNECTED BY 1/2"C.W.PER COUNTYWIDE | | AMENDMENTS TO PLBG.CODE SEC.607.7. | | | | CLEARLY SHOW H.W.SYSTEM ON RISER.SPC SEC | | 104.2.1. | | | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | SEC.610.4.1,610.4.2. | | | | SIZE ALL SECTIONS OF THE SANITARY AND | | WATER RISERS. | | | | SAN.RISERS ARE NOT TO CODE.COMPLY W/SPC | | SEC.909.3.2,COUNTYWIDE AMEND.TO STD. | | PLBG.CODE SEC.911.1.1 | | | | SINK IN BREAK ROOM AREA SHALL COMPLY W/ | | F.A.C.B.C.SECS.4.24,1-4.24.7. | | | | SIZE ALL SECTIONS OF THE WATER RISER TO | | ENSURE PROPER SIZING.SPC 104.2.1 | | | | WATER RISER SHALL CORRELATE W / FLOOR | | PLAN.SPC 104.2.1 |
|