2001-01-08 00:00:00NOTES***********************************
 FAN SHUT DOWN REQUIRED FOR AHU # 1 BY
 DUCT SMOKE DETECTOR PER SMC 406.2 WITH
 NOTIFICATION BY HORN AND STROBE PER 1996
 NFPA 4-4.4.3.