Plan Review Notes For Permit 99061392 |
Permit Number |
99061392 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | SUBMIT OCCUPANT LOAD TO DETERMINE MIN. | | REQ'D.PLBG.FIXTURES PER STD.PLBG.CODE | | SEC.407.1.3,TABLE 407. | | | | A DRINKING FOUNTAIN IS REQ'D.PER STD. | | PLBG.CODE TABLE 407. | | | | WALLS AND FLOORS OF PUBLIC RESTROOMS | | SHALL COMPLY W/STD.BUILDING CODE SEC. | | 1204.2. | | | | FIXTURE CLEARANCE OF H.C.WATER CLOSET | | FROM WALL SHALL COMPLY W/F.A.C.B.C.SEC. | | 4.17.2 AND FIGS.30(A)(B). | | | | WATER HEATER SHALL BE LOCATED TO BE | | READILY ACCESSIBLE FOR MAINTENANCE, | | SERVICING AND REPLACEMENT PER STD.PLBG. | | CODE SEC.501.7,SEC.202(DEFIN.),AND SEC. | | 507.8 OF STD.PLBG.CODE. | | | | PAN DRAIN AND RELIEF VALVE DRAIN SHALL | | NOT BE INTERCONNECTED PER STD.PLBG.CODE | | SEC.507.8.4 | | | | WATER SUPPLY CONTROL FOR FIXTURES P-5, | | P-6,& P-7 SHALL COMPLY W/STD.PLBG.CODE | | SEC.610.4.2. | | | | CLEANOUTS SHALL COMPLY W/STD.PLBG.CODE | | SEC.710.2.1. | | | | CLEARLY SHOW DIMENSIONS OF H.C.STALL | | ON ARCH.PLANS.COMPLY W/F.A.C.B.C.SEC. | | 4.17.3(SEE EXCEPTION -NEW CONSTRUCTION.) |
|