Plan Review Notes
Plan Review Notes For Permit 99061392
Permit Number 99061392
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT OCCUPANT LOAD TO DETERMINE MIN.
 REQ'D.PLBG.FIXTURES PER STD.PLBG.CODE
 SEC.407.1.3,TABLE 407.
  
 A DRINKING FOUNTAIN IS REQ'D.PER STD.
 PLBG.CODE TABLE 407.
  
 WALLS AND FLOORS OF PUBLIC RESTROOMS
 SHALL COMPLY W/STD.BUILDING CODE SEC.
 1204.2.
  
 FIXTURE CLEARANCE OF H.C.WATER CLOSET
 FROM WALL SHALL COMPLY W/F.A.C.B.C.SEC.
 4.17.2 AND FIGS.30(A)(B).
  
 WATER HEATER SHALL BE LOCATED TO BE
 READILY ACCESSIBLE FOR MAINTENANCE,
 SERVICING AND REPLACEMENT PER STD.PLBG.
 CODE SEC.501.7,SEC.202(DEFIN.),AND SEC.
 507.8 OF STD.PLBG.CODE.
  
 PAN DRAIN AND RELIEF VALVE DRAIN SHALL
 NOT BE INTERCONNECTED PER STD.PLBG.CODE
 SEC.507.8.4
  
 WATER SUPPLY CONTROL FOR FIXTURES P-5,
 P-6,& P-7 SHALL COMPLY W/STD.PLBG.CODE
 SEC.610.4.2.
  
 CLEANOUTS SHALL COMPLY W/STD.PLBG.CODE
 SEC.710.2.1.
  
 CLEARLY SHOW DIMENSIONS OF H.C.STALL
 ON ARCH.PLANS.COMPLY W/F.A.C.B.C.SEC.
 4.17.3(SEE EXCEPTION -NEW CONSTRUCTION.)