Notes |
Date |
Text |
2001-01-08 00:00:00 | ****************PROVISO**************** | | | | NOTE:SUBMIT PLANS WITH AIC RATING FIG. | | FROM FAULT CURRENT CALCULATIONS DRAW ON | | PANEL SCHED/RISER DIAGRAM.ART215-5 | | NOTE:PLANS SHOW GARAGE DOOR OPENER BUT | | G.D.O. IS NOT ON PANEL SCHED. AND IS NOT | | FIGUREDIN THE LOAD CACULATIONS. | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | OUTSIDE BEDROOMS. | | | | PLEASE RESUBMIT THE ABOVE INFORMATION | | BEFORE ROUGH INSPECTION IS CALLED IN. |
|