Plan Review Notes
Plan Review Notes For Permit 99061116
Permit Number 99061116
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00****************PROVISO*****************
  
 NOTE:NEED TO SUBMIT AIC RATING FIGURED
 FROM FAULT CURRENT CALCULATIONS.
 NOTE:NOTICE ON PLANS IT SHOWS 2ND.
 DISCONNECT BEING FED THROUGH FIRST
 DISC.DISCONNECT#1 NOT PERMITTED TO BE
 AS A RACEWAY.ART.373-8
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:GROUNDING ELECTRODE CONDUCTOR
 REQ`D TO GO TO BLDG.STEEL ALSO.
 NOTE:A COUPLE OF MISSING OUTLETS.AS PER
 ART'S:210-52H/210-52A
 NOTE:GARAGE DOOR OPENERS NOT FIGURED
 IN LOAD CACULATIONS.20A CIRCUT REQ`D
 OR SIZED FOR NAMEPLATE RATING.
  
 PLEASE HAVE THE ABOVE INFORMATION RE-
 SUBMITTED BEFORE ROUGH INSPECTION IS
 CALLED IN.