Plan Review Notes For Permit 99061116 |
Permit Number |
99061116 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ****************PROVISO***************** | | | | NOTE:NEED TO SUBMIT AIC RATING FIGURED | | FROM FAULT CURRENT CALCULATIONS. | | NOTE:NOTICE ON PLANS IT SHOWS 2ND. | | DISCONNECT BEING FED THROUGH FIRST | | DISC.DISCONNECT#1 NOT PERMITTED TO BE | | AS A RACEWAY.ART.373-8 | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | OUTSIDE BEDROOMS. | | NOTE:GROUNDING ELECTRODE CONDUCTOR | | REQ`D TO GO TO BLDG.STEEL ALSO. | | NOTE:A COUPLE OF MISSING OUTLETS.AS PER | | ART'S:210-52H/210-52A | | NOTE:GARAGE DOOR OPENERS NOT FIGURED | | IN LOAD CACULATIONS.20A CIRCUT REQ`D | | OR SIZED FOR NAMEPLATE RATING. | | | | PLEASE HAVE THE ABOVE INFORMATION RE- | | SUBMITTED BEFORE ROUGH INSPECTION IS | | CALLED IN. |
|