Date |
Text |
2001-01-08 00:00:00 | SHTS.C-9 & C-10.-CLEANOUTS IN BLDG. |
| SEWERS SHALL BE INSTALLED AND COMPLY W/ |
| STANDARD PLUMBING CODE SECS.710.2.4, |
| 711.2.2,711.2.3. |
| |
| SHT.C-11.-SUMP DETAIL SHALL COMPLY W/ |
| STD.PLBG.CODE SEC.717.2.(CONTINUATION |
| F SUMP DISCHARGE IS SHOWN ON C-7,NOT |
| C-4 AS NOTED.)CLARIFY SIZE OF DISCHARGE |
| LINE.DETAIL SHOWS 6" & NOTE STATES 3". |
| |
| SHT.IR-4.-PLANS SHOW WATER SUPPLY FOR |
| IRRIGATION SYSTEM FROM LAKE AND WELLS. |
| SUBMIT COPY OF CONSUMPTIVE WATER USE |
| PERMIT PER FLA.STATUTE 373.219. |
| |
| A WELL DRILLING PERMIT IS REQUIRED FROM |
| SO.FLA.WATER MNGMT.DISTRICT FOR THE |
| IRRIGATION WELLS PER FLA.STATUTE 373.342 |
| |
| SHT.P1.1-VACUUM BREAKERS AND GATE VALVES |
| ARE REQ'D.ON POLE HYDRANTS PER STD.PLBG. |
| CODE SEC.606.3.4.1.,610.4.1,610.4.2. |
| |
| SHT.P1.1-DETAIL #3-WATER SUPPLY CONTROL |
| SHALL COMPLY W/STD.PLBG.CODE SEC.610.4 |
| |
| SHT.P1.1-WATER SUPPLY CONTROL FOR HOT |
| WATER SHALL COMPLY W/STD.PLBG.CODE SEC. |
| 610.4.1.(CLARIFY 3/4" LINE SUPPLYING 1") |
| |
| SHT.P1.2-DETAIL#3-VENT SIZING DOESN'T |
| COMPLY W/TABLE 920.2 OF STD.PLBG.CODE. |
| (ALSO APPLIES TO SHT.1.1 DETAIL #2.) |
| |
| MIN.SIZE U/G DRAINAGE PIPE SHALL BE 2" |
| PER STD.PLBG.CODE SEC.714.4 (SEE EEW ON |
| SHT.P1.2 DETAIL#3). |
| |
| SUBMIT DETAIL OF INTERCEPTOR.COMPLY W/ |
| STD.PLBG.CODE SEC.1004. |
| |
| SUBMIT STORM/ROOF DRAINAGE RISER DIAGRAM |
| INDICATE SQ.FOOTAGE DRAINED BY EA.DRAIN. |
| COMPLY W/STD.PLBG.CODE SEC.1108,1109. |
| |
| INSTALLATION OF TRAP PRIMING DEVICES |
| SHALL COMPLY W/STD.PLBG.CODE SEC.614.4.6 |
| |
| SHT.P2.0-DETAIL#10.-FLOOR DRAIN IN PUMP |
| ROOM IS NOT VENTED.COMPLY W/STD.PLBG. |
| CODE SEC.908.1 |
| |
| ROOF FAUCETS SHALL BE VALVED PER STD. |
| PLBG.CODE SEC.610.4.1. |