Plan Review Notes For Permit 99060864 |
Permit Number |
99060864 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************DENIED/CORRECTED*********** | | 1) EXHAUST REQUIRED FROM JANITOR/UTILITY | | ROOM 1994 SMC 503.2 | | 2) PROVIDE OUTSIDE AIR CALCULATIONS PER | | ASHRAE 62-89 | | 3) PROVIDE AIR BALANCE SCHEDULE TO SHOW | | COMPLIANCE WITH 1994 SMC 501.2 | | JULY 10, 1999 |
|