Plan Review Notes For Permit 99060864 |
Permit Number |
99060864 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1)THE 2 ATS'S NEED TO HAVE MEANS OF | | DISCONNECT AT THE TRANSFER SWITCH | | PER 225-8, AND 230-72 | | (SUFFICIENTLY REMOTE FROM THE OTHER | | MAINS DOES NOT MEAN OUTSIDE BUILDING | | 10'TO 15' IS REMOTE. | | | | 2)MAINS ARE ABOVE THE OFFICE AREA. | | HOW ARE MAINS ACCESSED! | | | | 3)MAINS ON THE SECOND FLOOR LIMIT YOU | | TOO 8' OF SERVICE ENTRANCE CONDUCTOR | | IN EACH SET, INSIDE THE BUILDING | | | | 4)PANEL SCHEDULES R, R1, SB, IS1, AND | | IS2 ARE MISSING FROM THE DRAWINGS. | | | | 5)PROVIDE THIS ADDITIONAL INFORMATION | | PRIOR TO FIRST ELECTRICAL INSPECTION |
|