Plan Review Notes
Plan Review Notes For Permit 99060774
Permit Number 99060774
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001.ENERGY CALKS CALL FOR 14 SEER. A/C
 PLAN SHOWS ONE 14 SEER AND ONE 12 SEER.
 2.DROP MISSING IN POWDER ROOM.
 3.TOTAL CFMS. WITHOUT POWDER ROOM IS
 2040. A/H CAPACITY IS 2000.