Plan Review Notes
Plan Review Notes For Permit 99060720
Permit Number 99060720
Review Stop P
Sequence Number 5
Notes
Date Text
2001-01-19 00:00:00DENIED;
  
 THE FOLLOWING REVIEW NOTES FROM
 TIMOTHY LARGE HAVE NOT BEEN ADDRESSED.
  
 1.SUBMIT SQUIRE FOOTAGE OF SPACE FOR
 OCCUPANT LOAD TO ENSURE COMPLIANCE
 WITH SPC TABLE 407. SEE SPC SEC.
 407.1.3 FOR ALLOWABLE DEDUCTIBLE AREAS
  
 2.SHOW DIMENSIONS OF TOILET ROOMS COMPLY
 WITH FIG. 28 OFSACBC AND SHOW REQUIRED
 WHEELCHAIR TURNING SPACE IN TOILET
 ROOMS PER FACBC SEC. 4.2.3.
  
 3.SHOW FIXTURE CLEARANCES FOR HANDICAP
 FIXTURES PER SACBC SEE SEC. 4.15-4.19.
  
 4.URINAL SHALL BE INSTALLED AT HANDICAP
 HEIGHT AND COMPLY WITH SACBC SEC. 4.18.
 SHOW DETAILS OF ON DRAWINGS.
  
 5.A MAX. OF 4 FIXTURE UNITS ARE
 PERMITTED ON WET VENTS PER SPC 911.1
 (SEE URINAL / LAV.)
 SHTS. P-1 AND P-2 WHERE NOT WITH PLANS
  
 6.INDICATE SLOPE OF STORMWATER PIPING ON
 PLAN. COMPLY WITH TABLES 1108.1 AND
 1108.2 OF SPC.
  
 NOTE ON PAGE A-1 (PLUMBING ROUGH HAS
 BEEN INSTALLED) DOES NOT ALLOW
 CONTRACTOR TO CIRCUMVENT CODES.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377