Plan Review Notes For Permit 99060720 |
Permit Number |
99060720 |
|
Review Stop |
P |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2001-01-19 00:00:00 | DENIED; | | | | THE FOLLOWING REVIEW NOTES FROM | | TIMOTHY LARGE HAVE NOT BEEN ADDRESSED. | | | | 1.SUBMIT SQUIRE FOOTAGE OF SPACE FOR | | OCCUPANT LOAD TO ENSURE COMPLIANCE | | WITH SPC TABLE 407. SEE SPC SEC. | | 407.1.3 FOR ALLOWABLE DEDUCTIBLE AREAS | | | | 2.SHOW DIMENSIONS OF TOILET ROOMS COMPLY | | WITH FIG. 28 OFSACBC AND SHOW REQUIRED | | WHEELCHAIR TURNING SPACE IN TOILET | | ROOMS PER FACBC SEC. 4.2.3. | | | | 3.SHOW FIXTURE CLEARANCES FOR HANDICAP | | FIXTURES PER SACBC SEE SEC. 4.15-4.19. | | | | 4.URINAL SHALL BE INSTALLED AT HANDICAP | | HEIGHT AND COMPLY WITH SACBC SEC. 4.18. | | SHOW DETAILS OF ON DRAWINGS. | | | | 5.A MAX. OF 4 FIXTURE UNITS ARE | | PERMITTED ON WET VENTS PER SPC 911.1 | | (SEE URINAL / LAV.) | | SHTS. P-1 AND P-2 WHERE NOT WITH PLANS | | | | 6.INDICATE SLOPE OF STORMWATER PIPING ON | | PLAN. COMPLY WITH TABLES 1108.1 AND | | 1108.2 OF SPC. | | | | NOTE ON PAGE A-1 (PLUMBING ROUGH HAS | | BEEN INSTALLED) DOES NOT ALLOW | | CONTRACTOR TO CIRCUMVENT CODES. | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8377 |
|