Plan Review Notes
Plan Review Notes For Permit 99060720
Permit Number 99060720
Review Stop P
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:001)SUBMIT SQUARE FOOTAGE OF SPACE FOR
 OCCUPANT LOAD TO ENSURE COMPLIANCE WITH
 SPC TABLE 407.SEE SPC SEC.407.1.3.FOR
 ALLOWED DEDUCTIBLE AREAS.
  
 2)SHOW DIMENSIONS OF TOILET ROOMS.COMPLY
 W/FIG.28 OF FACBC AND SHOW REQD.WHEEL-
 CHAIR TURNING SPACE IN TOILET ROOMS PER
 FACBC SEC.4.2.3.
  
 3)SHOW FIXTURE CLEARANCES FOR HANDICAP
 FIXTURES PER FACBC.SEE SECS.4.15-4.19.
  
 4)URINAL SHALL BE INSTALLED AT H.C.
 HEIGHT AND COMPLY W/FACBC SEC.4.18.
  
 5)A MAX.OF 4 FIXTURE UNITS ARE PERMITTED
 ON WET VENTS PER SPC 911.1(SEE URINAL/
 LAV.)
  
 6)SHOW COMPLETE SIZE OF SCUPPERS AND
 SUBMIT DETAIL.COMPLY W/SPC APPENDIX"A"
 FOR SECONDARY DRAINAGE REQS.
  
 7)INDICATE SLOPE OF STORMWATER PIPING ON
 PLAN.COMPLY W/TABLES 1108.1 & 1108.2 OF
 SPC.
  
 8)ROOF DRAINAGE CALCULATIONS SHALL
 INCLUDE 1/2 THE AREA OF ANY VERTICAL
 WALLPER SPC SEC.1108.3.
  
 9)A DRINKING FOUNTAIN IS REQD.ON THE 2ND
 FLOOR PER SPC TABLE 407.
  
 10)COMPILE PLANS INTO 2 SETS.IT APPEARS
 THE ARCH. DRAWINGS ARE ONLY IN ONE SET.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 11)VOID OLD PLUMBING SHEETS.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.