2001-01-08 00:00:00THIS PLAN REVIEW WAS FOR THE EXIT STAIRS
 PLANNED FOR THE SOUTH SIDE OF THE
 BUILDING.
  
 1) PLEASE PROVIDE DETAILS ON FIRE RATED
 WINDOWS AND FRAMES TO THIS OFFICE.
 2) STAIRS ARE TO BE SLIP RESISTANT.
 3) STAIRS TO MEET ALL OF THE
 REQUIREMENTS FOR NEW STAIRS PER NFPA
 101, THE LIFE SAFETY CODE, 1985
 EDITION. THE STAIRS ARE ALLOWED TO BE
 36" WIDE BASED ON OCCUPANT LOADS OF
 LESS THAN 50 PERSONS.
 4) PLEASE SUBMIT SHOP DRAWINGS FOR THE
 STAIRS.
 5) ANY AND ALL OPENINGS WITHIN 10 FEET
 OF THE STAIRS ARE TO BE PROTECTED BY
 FIRE RATED WINDOWS AND DOORS.
 6) HOW IS STAIR SUPPORTED AND FASTENED
 TO THE BUILDING.
 7) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, THE LIFE SAFETY CODE,1985
 EDITION.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910