Plan Review Notes
Plan Review Notes For Permit 99060289
Permit Number 99060289
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************PROVISO*******************
  
 NEED TO SUBMIT FAULT CURRENT CACULATIONS
 AND HAVE AIC RATING DRAWN ON PANEL SCHD.
 ART.215-5
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:ALL RECEPTS.SERVING KITCHEN
 COUNTER ARE TO BE GFI/GFI PROTECTED.
 ART.210-8-A-6
 NOTE:GROUNDIG ELECTRODE CONDUCTOR
 TO GRND. ROD,BLDG.STEEL.
  
 NEED TO HAVE ABOVE INFORMATION BEFORE
 ROUGH INSPECTION.