2001-01-08 00:00:00 | ***************PROVISO****************** | | | | NOTE:NEED TO SUBMIT PLANS WITH AIC | | RATING DERIVED FROM FAULT CURRENT | | CALCULATIONS.215-5 | | NOTE:RECEPTS.SERVING KITCHEN COUNTER | | SPACE ARE TO BE GFI/GFI PROTECTED. | | ART.210-8-A-6 | | NOTE:GROUNDING ELECTRODE CONDUCTOR | | ALSO CONNECTED TO BLDG.STEEL. | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | OUTSIDE BEDROOMS. | | NOTE:REQ`D RECEPTS.MISSING.210-52A | | | | NEED TO SUBMIT REVISED PLANS BEFORE | | ROUGH INSPECTION. |
|