Plan Review Notes
Plan Review Notes For Permit 99060111
Permit Number 99060111
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00****************PROVISO*****************
  
 NEED FAULT CURRENT CALCULATIONS AND
 AIC RATING TO BE DRAWN ON PLANS.
 ART.215-5
 NOTE:SMOKE DETECTORS REQ`D INSIDE
 AND OUTSIDE BEDROOMS.
 NOTE:GROUNDING ELECTRODE SYSTEM TO GO
 TO BLDG.STEEL ALSO.
  
 NEED THE ABOVE INFORMATION BEFORE
 ROUGH INSPECTION IS CALLED.