Plan Review Notes
Plan Review Notes For Permit 99060020
Permit Number 99060020
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00BIDET DOWNSTREAM OF W.C.SHALL BE VENTED.
 SPC SEC.913.2.
  
 MIN.SIZE OF U/G DRAINAGE PIPING SHALL BE
 2" PER SPC SEC.714.4.
  
 FLOOR PLAN INDICATES 1 LAV. IN M.B.&
 SANITARY RISER DEPICTS 2. CLARIFY.
 SPC 104.2.1.