Plan Review Notes For Permit 99051186 |
Permit Number |
99051186 |
|
Review Stop |
P |
Sequence Number |
8 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1)3"STACK TO 2ND FLOOR CANNOT CONNECT TO | | THE CIRCUIT AND LOOP SYSTEM FOR THE 2ND. | | FLOOR PER SPC SEC.914.1. | | | | 2)SHT.P-7-THE GREASY WASTE SYSTEM SHALL | | BE DESIGNED TO COMPLY W/SPC SEC.921.(A | | VENT IS ALSO REQD.DOWNSTREAM OF THE | | FIRST FIXTURE DRAIN ON THE SYSTEM.) | | | | 3)A MANUAL SHUT-OFF VALVE IS REQD.AT THE | | SOLENOID VALVE W/A UNION DOWNSTREAM OF | | SOLENOID VALVE PER NFPA SEC.5.5.4. | | | | 4)SHOW REQD.VALVE UPSTREAM OF MP REG.FOR | | WATER HEATERS PER NFPA SEC.3.10.1. | | | | 5)INDICATE TABLE UTILIZED TO SIZE 2 PSI | | SYSTEM TO WATER HEATERS. | | | | 6)REGULATORS SHALL BE VENTED TO ATMOS- | | PHERE PER NFPA 54 SEC.2.8.4. | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | ANY QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|