2001-01-08 00:00:001)3"STACK TO 2ND FLOOR CANNOT CONNECT TO
 THE CIRCUIT AND LOOP SYSTEM FOR THE 2ND.
 FLOOR PER SPC SEC.914.1.
  
 2)SHT.P-7-THE GREASY WASTE SYSTEM SHALL
 BE DESIGNED TO COMPLY W/SPC SEC.921.(A
 VENT IS ALSO REQD.DOWNSTREAM OF THE
 FIRST FIXTURE DRAIN ON THE SYSTEM.)
  
 3)A MANUAL SHUT-OFF VALVE IS REQD.AT THE
 SOLENOID VALVE W/A UNION DOWNSTREAM OF
 SOLENOID VALVE PER NFPA SEC.5.5.4.
  
 4)SHOW REQD.VALVE UPSTREAM OF MP REG.FOR
 WATER HEATERS PER NFPA SEC.3.10.1.
  
 5)INDICATE TABLE UTILIZED TO SIZE 2 PSI
 SYSTEM TO WATER HEATERS.
  
 6)REGULATORS SHALL BE VENTED TO ATMOS-
 PHERE PER NFPA 54 SEC.2.8.4.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.