Plan Review Notes For Permit 99051186 |
Permit Number |
99051186 |
|
Review Stop |
P |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | WATER HEATERS LOCATED ABOVE THE FIRST | | FLOOR CEILING SHALL BE EQUIPPED W/PANS | | AND DRAINS PER COUNTYWIDE AMENDMENTS TO | | SPC SEC.507.8.1. | | | | SHUT OFF VALVES ARE REQD.ON WATER SUPPLY | | BRANCH LINES PER SPC SEC.610.4.2. | | | | MAXIMUM OF 4 FIXTURES SHALL BE SUPPLIED | | BY 1/2" H.W.LINE PER COUNTYWIDE AMEND- | | MENTS TO SPC SEC.607.7. (SEE 4TH.FLR. | | RESTROOMS & CHECK ENTIRE RISER.) | | | | FLOOR DRAINS SHALL BE LOCATED TO BE IN | | FULL VIEW PER SPC SEC.409.4.1.2. | | | | SHOW LENGTHS OF ALL CUT SECTIONS OF NEW | | GAS PIPE.NOTE APPROPRIATE GAS SIZING | | CHART ON PLAN.SYSTEM SIZING SHALL BE | | FROM POINT OF DELIVERY(EXISTING)TO MOST | | REMOTE OUTLET PER SGC SEC.305.4, 305.6. | | 1003.4.SUBMIT CALCULATIONS FOR SIZING. | | | | SHOW EMERGENCY SHUT-OFF VALVE FOR GAS | | SYSTEM PER NFPA 96, SEC.7-4. | | | | GAS EQUIPMENT SHUTOFF VALVES AND CONN- | | ECTIONS SHALL COMPLY W/NFPA 54,SEC.5.5.4 |
|