Plan Review Notes For Permit 99051186 |
Permit Number |
99051186 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | PLAN REVIEW FOR FIRST FLOOR LIFE SAFETY | | DRAWING. | | 1) IF ALL OF THE EXIT DOORS IN THE | | HORIZONTAL PLANE ARE AT LEAST 36" WIDE, | | THEY PROVIDE 1 1/2 UNITS OF EXIT WIDTH | | AND CAN PROVIDE EXITING FOR 150 PERSONS. | | 2) PLAN DOES NOT INDICATE WHAT PURPOSE | | THE PRE-FUNCTION LOBBY SERVES AND WHAT | | IF ANY OCCUPANT LOADS ARE EXPECTED FROM | | THIS AREA. | | 3) PLAN DOES NOT INDICATE RATED FIRE | | WALL LOCATIONS FOR CORRIDORS PRE- | | FUNCTION 106 AND 111. SINCE THESE | | THESE PROVIDE EXITING FOR 30 OR MORE | | PERSONS ONE HOUR FIRE SEPARATION IS | | REQUIRED. OPENINGS ARE TO BE PROTECTED | | WITH RATED FIRE DOORS. | | 4) EXIT SIGNS SHOULD BE INCLUDED WITH | | PLANS SO EXITING LOCATIONS ARE CLEARLY | | IDENTIFIED. |
|