Plan Review Notes For Permit 99051186 |
Permit Number |
99051186 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | PG.E-4 100 AMP DISC IN CORNER MUST MEE | | 110-26. | | | | PG.E-9 LOADS ON PANEL "ACB" SHOWS NO | | MOTOR CONTIBUTION PER 430-24,25,26 | | | | PG.E-13 "K" PANEL SHOWS THE OUTLETS AN | | VENTILATING EQUIPMENT INCLUDED IN THE | | DEMAND FOR THE THE KITCHEN EQUIP.SEE | | 220-22 FOR REQUIREMENTS!!!!!!!!!!!!!! | | | | PG.E-13 THE LOAD CALCULATION FOR "MDP" | | SHOWS LOADS THAT DO NOT MATCH WHAT IS | | SHOWN ON THE INDIVIDUAL PANELS LOAD CALC | | "ACB","A","B" SHOW LARGER THAN WHAT IS | | SHOWN ON THE CALC FOR "MDP"!!!!!!!!!!!! | | | | PG.E-13PANELS "A,B" SHOW A 200A DISC | | WITH A LOAD OF 25,000VA HOW WAS THIS | | FIGURED?200AMPS AT 208 = 72,000 VA | | | | PG.E-13 ALL PANELS AND DISC. ON LOAD | | SIDE OF THE MDP SHOW NO AIC RATING!!!! | | | | PLEASE CHECK ALL LOAD CALCULATIONS FOR | | COMPLIANCE WITH THE CODE!!!!!BASED ON | | WHAT IS SHOWN THE 3000 AMP MAIN IS TOO | | SMALL!!! |
|