2001-01-08 00:00:00SHT A2.1-AN ADD'L.HANDICAP STALL IS
 REQ'D.IN ROOM#113 PER F.A.C.B.C.SEC.
 4.22.4.
  
 COMMON LAUNDRY AREAS SHALL COMPLY W/
 F.A.C.B.C. SEC.4.1.6.9 (1)(B),4.27.1.
  
 HANDICAP SHOWERS AND SEATS SHALL COMPLY
 W/F.A.C.B.C. SEC.4.21.2, 4.21.3.
  
 SHT.A7.2-ELEV.#8-HANDICAP URINAL SHALL
 COMPLY W/F.A.C.B.C.SEC.4.18.2 (MAX.17"
 A.F.F.)
  
 SHT.A7.3-ADDITIONAL H.C. STALL REQ'D.
 IN MEN'S AND WOMEN'S RESTROOMS PER
 F.A.C.B.C. SEC.4.22.4.**(NOTE:CHECK ALL
 RESTROOMS FOR THIS REQ'.)
  
 SHT.A7.3-ELEV.#19-H.C URINAL SHALL BE
 AT MAX.17" A.F.F.TO RIM PER F.A.C.B.C.
 SEC.4.18.2.
  
 FLOOR DRAINS SHALL NOT EXCCED DISTANCE
 FROM VENT PER SPC.SEC.908 & TABLE 908.1
  
 MAX.TEMPERATURE OF WATER DISCHARGED TO
 SANITARY SYSTEM SHALL NOT EXCEED 140
 DEGREES.SPC.SEC.807.3
  
 MAX.TEMPERATURE TO RESTROOMS SHALL NOT
 EXCEED 110 DEGREES PER FLA.ENERGY CODE
 SEC.412.ABCD.2.3.2.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1, 610.4.2.
  
 FLOOR DRAINS ARE NOT PROPERLY VENTED.
 COMPLY W/SPC SEC.901.2, TABLE 908.1
  
 SUBMIT STORM RISER DIAGRAM FOR THE
 STORM DRAINAGE SYSTEM.SPC 104.2.1.
  
 SUBMIT MANUF.SHEETS FOR GASEQUIPMENT.
 EQUIPMENT SHALL BE LISTED PER STD.GAS
 CODE SEC.402.1.
  
 CLEARLY SHOW WATER SOURCE FOR IRRIGATION
 SYSTEM .BACKFLOW PREVENTION DEVICE IS
 REQ'D.IF ON CITY WATER.SPC 601.6
  
 EQUIPMENT SUPPLY LINES ON GAS HEADER ARE
 UNDERSIZED.COMPLY W.STD.GAS CODE SEC.
 305.2(INDICATE TYPE OF PIPING TO BE
 INSTALLED.)AND TABLES 305.4.
  
 SUBMIT CALCULATIONSFOR ROOF DRAINAGE
 OVERFLOW.COMPLY W/SBC SEC.1507.4.3,
 1604.6.2.,STD.PLBG.CODE SEC.1109.
  
 SUPPLY OCCUPANT LOAD AS DETERMINED BY
 SPC SEC.407.1.3 TO ENSURE COMPLIANCE
 FOR MINIMUM FIXTURE REQUIREMENTS.