2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SEE LOAD CALCULATIONS FOR
 PANEL "B" LOAD SHOWN FOR PANEL"G" DOES
 NOT CORRELATE WITH WHAT IS SHOWN ON "B"
 SCHEDULE. PLEASE NOTE THAT THE LOADS
 TOTALLED FROM ALL PANELS EXCEED RATING
 OF 3000 AMP MAIN. THIS WAS A CONCERN
 WHEN DOING PLAN REVIEWS IN THE BEGINING
 AND THOSE LOADS WERE TAKEN OFF. NOW
 LOAD EXCEEDS MAIN SERVICE SIZE.
  
 PLEASE NOTE THAT ALL LOAD CALCULATIONS
 WILL NEED TO BE SUBMITTEDAND SHOWN.
 ALL LOAD CALCULATIONS ARE TO BE DONE
 ACCORDING NEC AND IF SERVICE IS NOT OF
 SUFF. SIZE THEN SERVICE WILL NEED TO BE
 INCREASED. ALSO PLEASE NOTE THAT A MEET-
 -ING IS GOING TO BE REQUESTED FOR ANY
 INCREASE IN SERVICE AND FOR ANY QUESTION
 -S AND/OR VERIFICATION OF LOAD CALCS.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMAITON
 SIGNED AND SEALED BY ENGINEER OF RECORD
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  