Plan Review Notes For Permit 99051186 |
Permit Number |
99051186 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | UNSAT | | (1) COVER SHT.GIVE DETAILS OF OCCUPANCY | | & SQUARE FOOTAGE FOR EACH FLOOR AND | | NUMBER OF PEOPLE. | | (2) SHT.L-1 IRRIGATION LAYOUT AND | | LOCATION OF BACK FLOW PREVENTER. | | (3) SHT. P-2 SHOW 2ND FLOOR REST RM'S | | (4) SHT. P-6 ALL INDIRECT WASTE TO | | FLOOR SINKS NO HUB DRAINS.SPC CH 8. | | (5) SHT.P-8 GAS SOLENOID,A MANUAL | | SHUT OFF VALVE UP STREAM, UNION DOWN | | STREAM OF THE SOLENOID VALVE.SGC 508.2 | | (6) SHT P-8 CK GAS PIPE SIZE ON HEADER, | | FOR BTU LOAD OF EACH APPLIANCE. | | "UNDER SIZED" | | END OF COMMENTS |
|