Plan Review Notes
Plan Review Notes For Permit 99051186
Permit Number 99051186
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00UNSAT
 (1) COVER SHT.GIVE DETAILS OF OCCUPANCY
 & SQUARE FOOTAGE FOR EACH FLOOR AND
 NUMBER OF PEOPLE.
 (2) SHT.L-1 IRRIGATION LAYOUT AND
 LOCATION OF BACK FLOW PREVENTER.
 (3) SHT. P-2 SHOW 2ND FLOOR REST RM'S
 (4) SHT. P-6 ALL INDIRECT WASTE TO
 FLOOR SINKS NO HUB DRAINS.SPC CH 8.
 (5) SHT.P-8 GAS SOLENOID,A MANUAL
 SHUT OFF VALVE UP STREAM, UNION DOWN
 STREAM OF THE SOLENOID VALVE.SGC 508.2
 (6) SHT P-8 CK GAS PIPE SIZE ON HEADER,
 FOR BTU LOAD OF EACH APPLIANCE.
 "UNDER SIZED"
 END OF COMMENTS