Plan Review Notes For Permit 99051186 |
Permit Number |
99051186 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *************PROVISO******************** | | 1) STORAGE CLOSETS WITH JANITOR SINKS TO | | HAVE EXHAUST FROM SPACE SEE AC-1 STORAGE | | ROOM 103 PER 1994 SMC 501.4 | | 2) DUCTS PENETRATING RATED WALLS TO HAVE | | FIRE DAMPERS AT PENETRATION PER 1994 SMC | | 610.1 SEE ELEC ROOM ON AC-2 |
|