Plan Review Notes
Plan Review Notes For Permit 99051064
Permit Number 99051064
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SHOWER SHALL BE A MIN.OF 30" WIDE PER
 MODEL COUNTYWIDE AMEND.SEC.409.8.2.1.
  
 FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC SEC.913.2.
  
 SIZE VTR.FOR LAV.IN M.B.SPC.SEC.920.2
  
 MAX.2 W.C.'S PERMITTED ON 3" BUILDING
 DRAIN.SPC TABLE 714.1,FOOTNOTE#3.
  
 HORIZONTAL WET VENTS SHALL RECEIVE
 DISCHARGE FROM FIXTURE DRAINS ONLY PER
 MODEL COUNTYWIDE AMEND.SEC.911.1.1.
  
 ENERGY CALCS.SHOW CAPCITY OF EWH AS 30
 GAL.&PLANS SHOW 50 GAL.CLARIFY.