Plan Review Notes
Plan Review Notes For Permit 99050869
Permit Number 99050869
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00REMOVE TRAPS FROM WATER CLOSETS ON SAN.
 ISOMETRIC.SPC SEC.1001.6,1001.8.
  
 SIZE ALL SECTIONS OF THE DWV SYSTEM.
 SPC 104.2.1.
  
 MAX.2 WATER CLOSETS PERMITTED ON 3"
 BUILDING DRAIN.SPC TABLES 714.1,FOOTNOTE
 #3,TABLE 714.2,FOOTNOTE #2.
  
 MIN.SIZE OF BLDG.SEWER SHALL BE 4" PER
 SPC TABLE 714.1,FOOTNOTE#2.
  
 MIN.SIZE OF U/G SAN.DRAINAGE SHALL BE
 2".SPC 714.4.
  
 "S-TRAP" ON KIT.SINK NOT PERMITTED PER
 SPC SEC.101.5.2.,901.2.
  
 TUBS NOT PROPERLY VENTED.SPC 901.2.
  
 WET VENTS SHALL RECEIVE DISCHARGE FROM
 FIXTURE DRAINS ONLY.COUNTYWIDE AMEND.TO
 STANDARD PLBG.CODE SEC.911.1.1.