2001-01-08 00:00:00***************PROVISO*****************
  
 NEED CALCULATIONS DONE FOR AIC RATING
 WHICH NEEDS TO BE DRAWN ON PANEL SCHD.
 ART.215-5
 NEED RISER DIAGRAM TO SHOW GROUNDING
 ELECTRODE CONDUCTOR DRAWN TO GROUND ROD,
 C.W.P.,AND BLDG.STEEL.215-5
 NOTE:NEED EQUIPMENT GROUNDING COND.
 DRAWN ON PLANS FROM MAIN DISC.TO
 PANEL AND FROM PANEL TO OTHER DISC.S
 250-92/250-95
 NOTE:SMOKE DETECTORS REQ`D INSIDE
 AND OUTSIDE BEDROOMS.
 NOTE:RECEPTS.SERVING KITCHEN COUNTER
 TOPS ARE TO BE DRAWN GFI/GFI PROTECTED.
 ART.210-8-A-6
 NOTE:MASTER BEDROOM HALL 210-52H
 NOTE:2`6`12`RULE 210-52A
  
 NEED TO SUBMIT BEFORE ROUGH INSPECTION!!