2001-01-08 00:00:00**************PROVISO*******************
  
 SUBMIT!!!NEW PANEL SCHEDULE WITH AIC
 RATING.!!!!
 RISER DIAGRAM NEEDS TO SHOW WIRE SIZES
 ALSO GROUNDING ELECTRODE SYSTEM TO C.W.P
 ALL ABOVE ART.215-5
  
 ALL ABOVE NEEDS TO BE DONE BEFORE
 ROUGH INSPECTIONIS CALLED IN!!!!!!!!!!