Plan Review Notes
Plan Review Notes For Permit 99050509
Permit Number 99050509
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CLEARLY SHOW LOCATION OF DRINKING
 FOUNTAIN ON PLANS.SPC 104.2.1.
  
 DRINKING FOUNTAIN SHALL COMPLY
 W/F.A.C.B.C. SEC.4.3.1.,4.1.3.(10) (A),
 4.15.1 THRU 4.15.5.SUBMIT ELEV.DETAIL
 OF DRINKING FOUNTAIN.
  
 INDICATE OCCUPANT LOAD TO DETERMINE
 MINIMUM NUMBER OF REQ'D.FACILITIES PER
 EC.407.1.1 THRU 407.2.2.OF SPC.
  
 NOTE ON PLAN THAT NEW PLBG.FIXTURES
 COMPLY W/TABLE 406 OF SPC FOR WATER
 CONSERVATION.
  
 CLEARLY SHOW SIZE OF BUILDING SEWER.
 COMPLY W/SPC TABLE 714.1,FOOTNOTE #2.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1
  
 CLEARLY SHOW LOCATION OF BFP DEVICE ON
 DOMESTIC WATER SERVICE PER SPC SEC.606.1
 SUBMIT MANUF.DATA FOR MAKE & MODEL OF
 BACKFLOW PREVENTION DEVICES.SPC SEC.
 606.2.INSTALLATION SHALL COMPLY W/SPC
 SEC.606.4.1.,606.5.
  
 SHT.F-1-CLEARLY SHOW TERMINATION POINTS
 OF 3" WASTE,2" BACKWASH,& 2" FILTER
 DISCHARGE LINE FROM FOUNTAIN.SPC SEC.
 104.2.1,705.1.
  
 SHT.F-1-ALL PIPE SIZES ON FOUNTAIN
 PIPING SHALL BE LEGIBLE.SPC 104.2.1.
  
 SUBMIT PIPING DIAGRAM & DETAIL OF SUMP
 SHOWN ON SHT.F-1.COMPLY W/SPC SECS.717.2
 717.9.1.
  
 SEE PLUMBING PERMIT # 99050514