Plan Review Notes For Permit 99050066
Permit Number 99050066
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT CIVIL DRWGS.AS NOTED ON SHT.P-1
 THAT CLEARLY SHOW CONNECTION OF SANITARY
 AND WATER LINES TO CITY UTILITIES.
 SPC SEC.104.2.1,104.3.1.
  
 SHT.A-2 SHOWS ROOF DRAINS-SUBMIT STORM
 WATER RISER FOR REVIEW.SUPPLY SQ.FT.AREA
 DRAINED BY EACH DRAIN,PIPE SIZES,SLOPE
 OF PIPE,TERMINATION PT.,ETC. SPC.SEC.
 1101.2.TYPE OF PIPING SHALL COMPLY W/SPC
 SEC.1103.4, 1104.
  
 SUBMIT PROVISIONS FOR SECONDARY DRAINAGE
 OF ROOF AREA WHERE ROOF DRAINS ARE
 LOCATED. SPC SEC.1109.1
  
 SLOPE OF SANITARY SYSTEM SHALL COMPLY
 W/SPC SEC.705.2,705.3.(SEE NOTE #8 ON
 SHT.P.1.)
  
 SHT.P.1-NOTE #11-"M" COPPER NOT
 PERMITTED BELOW GROUND PER COUNTYWIDE
 AMENDMENTS SEC.611.3.
  
 SHT.P.1-NOTE #16 REFERS TO GAS.SUBMIT
 PLANS FOR GAS IF APPLICABLE.IF NO GAS
 DELETE NOTEFROM PLAN.
  
 SHT.P1-MIN.DISTANCE BETWEEN BUILDING
 DRAIN /SEWER AND WATER SERVICE SHALL
 COMPLY W/SPC SEC.608.3
  
 CONDENSATE DRAINS SHALL DISCHARGE PER
 STD,MECH.CODE SEC.304.8.3 & COUNTYWIDE
 AMENDMENTS TO SPC.SEC.804.3.
  
  
 ****************PROVISO*****************
 SECONDARY DRAINAGE PROVISIONS SHALL BE
 PROVIDED FOR LOW ROOF AREA AND COMPLY W/
 STANDARD BUILDING CODE SECS.1507.4.1,
 THRU 1507.4.3, 1604.6.2(1-4),AND
 STANDARD PLUMBING CODE SEC.1109.1,
 1109.2, 1109.3.
  
 PLANS AND RISER DIAGRAM REQ'D.PRIOR TO
 RGH.PLBG.INSP.6/30/99.