Plan Review Notes
Plan Review Notes For Permit 99041328
Permit Number 99041328
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO*******************
  
 NOTE:PRINT SHOWS MAIN DISC..IF SO THEN
 NEEDS TO BE DRAWN ON RISER DIAGRAM!!!
 ART.215-5
 NOTE:NEED FAULT CURRENT CALCULATIONS
 FOR AIC RATING.215-5
 NOTE:GROUNDING ELECTRODE COND.TO GROUND
 ROD AND BLDG.STEEL.
 NOTE:210-8-A-6 REQ`MENTS FOR RECEPTS.
 SERVING KITCHEN COUNTER TO BE GFI/OR
 PROTECTED.
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:ART.210-52A OUTLET SPACING.2`6`12`
 RULE.
  
 NEED CHANGES BEFORE ROUGH INSPECTION
 IS CALLED IN!!!!