Plan Review Notes
Plan Review Notes For Permit 99041194
Permit Number 99041194
Review Stop P
Sequence Number 5
Notes
Date Text
2001-01-08 00:00:00******************PROVISO***************
 DESIGN OF GREASE INTERCEPTOR SHALL
 COMPLY W/ CITY OF WEST PALM BEACH
 UTILITIES REQS.CONTACT R.COMPO AT
 (561) 835-7423.
  
 SHT.CP-3.06-CONNECTION OF CONDENSATE TO
 STORM DRAIN SHALL BE BY INDIRECT
 CONNECTION PER SPC SEC.804.3,807.2.
  
 FLOOR DRAINS AT COMPACTOR SHALL BE A
 MAXIMUM OF 15' FROM THE VENT,NOT A MIN.
 OF 15'.COUNTYWIDE AMENDMENTS TO SPC SEC.
 908.1,FOOTNOTE #1.
  
 SUBMIT DETAIL OF GAS MANIFOLD.THE
 MANIFOLD IS LOCATED NEXT TO A
 TRANSFORMER PAD THAT WILL SERVE EQUIP-
 MENT THAT MAY BE CONSIDERED A SOURCE OF
 IGNITION.SUBMIT INFO ON EQUIPMENT BEING
 LOCATED ON PAD.COMPLY W/NFPA 54,SEC.1.7.
  
 SHT.CMP-3.01-VTR IS LOCATED WITHIN 10'
 OF OAI-COMPLY W/SPC SEC.905.5.