2001-01-08 00:00:00 | ******************PROVISO*************** | | DESIGN OF GREASE INTERCEPTOR SHALL | | COMPLY W/ CITY OF WEST PALM BEACH | | UTILITIES REQS.CONTACT R.COMPO AT | | (561) 835-7423. | | | | SHT.CP-3.06-CONNECTION OF CONDENSATE TO | | STORM DRAIN SHALL BE BY INDIRECT | | CONNECTION PER SPC SEC.804.3,807.2. | | | | FLOOR DRAINS AT COMPACTOR SHALL BE A | | MAXIMUM OF 15' FROM THE VENT,NOT A MIN. | | OF 15'.COUNTYWIDE AMENDMENTS TO SPC SEC. | | 908.1,FOOTNOTE #1. | | | | SUBMIT DETAIL OF GAS MANIFOLD.THE | | MANIFOLD IS LOCATED NEXT TO A | | TRANSFORMER PAD THAT WILL SERVE EQUIP- | | MENT THAT MAY BE CONSIDERED A SOURCE OF | | IGNITION.SUBMIT INFO ON EQUIPMENT BEING | | LOCATED ON PAD.COMPLY W/NFPA 54,SEC.1.7. | | | | SHT.CMP-3.01-VTR IS LOCATED WITHIN 10' | | OF OAI-COMPLY W/SPC SEC.905.5. |
|